AESO Black Start Studies

The adjacent plot shows the start of a 7000HP boiler feed water pump and the resulting voltage response. It is apparent that the local source is unable to provide the necessary var support for the system and thus the voltage collapses. Surprisingly, the motor is able to start, resulting in a large overvoltage and subsequent oscillation. This scenario, if attempted, would undoubtedly trip out on undervoltage.